Masoneilan SVI II AP Digital Positioner Quick Start Guide =| 53© 2015 General Electric Company. All rights reserved.Check-out with a HART® Handheld CommunicatorIf the SVI II AP is not equipped with optional push buttons and local display the checkout and con-figuration is performed using the standard HART® communications interface.Connect the HART® handheld communicator to the SVI II AP as shown in Figure 27. Refer to theproduct manual for the HART® communicator in use.Figure 27 SVI II AP HART® Communicator ConnectionsBe sure that the configuration lock jumper is in the unlock position. When the jumper is in the lockposition (shorting the two-pin header) the handheld is not permitted to make any changes. How-ever, parameters are readable. If fault messages appear, they must be handled before proceed-ing with HART® communications. Before communications proceeds all error messages must becleared. For example, the following message is displayed if the instrument has been serviced andthe air is not connected.Process applied to the non-primary variable is outside theoperating limits of the field deviceNOTE For HART® 6 units, the Maintenance Required response underAdditional Status does not indicate any maintenance need.+ -12.00 mAConfigurationLock JumperInput SignalDPI620