Masoneilan SVI II AP Digital Positioner Quick Start Guide =| 59© 2015 General Electric Company. All rights reserved.Physical and Operational SpecificationsThis section provides the physical and operational specifications for the SVI II AP.Specifications are subject to change without notice.Table 8: Environmental SpecificationsOperating Temperature Limits -58° F to 185° F (-50° C to 85° C)Storage Temperature Limits -58° F to 200° F (-50° C to 93° C)Temperature Effect < 0.005% / °F typical; -40° F to 180° F (< 0.01% / °C typical;-40° C to 82° C)Supply Pressure Effect 0.05% per psi (.73% per bar)Relative Humidity 10 to 90% non-condensingHumidity Effect Less than 0.2% after 2 days at 104 °F (40° C), 95% Relative Humidity.Insulation Resistance Greater than 10 G Ohms at 50% RH.MTBF 49 years based on MIL handbook calculation for electronic parts andfield data on mechanical partsElectromagnetic CompatibilityElectrostaticElectrostatic discharge ― No effect with contact discharge level of 4KVand air discharge level of 8 kV (IEC 1000-4-2)Radio frequency interference ― Less than 0.2% at 10 V per meter (EN50140)Fast Transient Burst No effect at 2 kV (Coupling clamp IEC 1000-4-4).Vibration InfluenceMeasured at SVI II AP Housing4 mm at 5 - 15 Hz - Negligible2 G at 15 - 150 Hz Less than 2 % of span1 G at 150 - 2000 Hz - Less than 2% of spanMagnetic Field Influence Negligible at 30 A/m (EN61000-4-8)CE MARK certified to EN50081-2 and EN50082-2A. Specifications andReferences