GEmodifications reserved Page 10/10OPM_VCL_XXX_0K4_1K5_XGB_V012 User manual - VCL Series UPS 400-1500VA V012 - GB4 SPECIFICATIONSModel : VCL400 VCL600 VCL800 VCL1000 VCL1500Rating VA/W : 400/250 600/360 800/480 1000/600 1500/900AC input voltage window : 170 ~ 280VacFrequency : 50 / 60 Hz auto sensingBattery type : 12V, sealed lead acid, maintenance freeNumber x capacity of battery : 1x4.5Ah 1x7Ah 1x9Ah 2x7Ah 2x9AhBattery recharge time : 8 hours typicalRuntime in minutes at typical load (60%) : 5 6 6 8 6Internet / phone / fax protection : RJ-11 (One pair), 2C; 114 joules; clamping rate 330VCommunication port : USB (RJ11)Ambient temperature : 0°C ~ 40°C (+32°F ~ 104°F)Maximum relative humidity : 95% (non-condensing)Storage temperature : -15°C ~55°C (+5°F ~ 131°F)Net weight (kg) : 4.0 4.6 5.6 8.4 10.3Dimensions (hxwxd, mm) : 220x112x222 220x112x330This document shall not be copied nor reproduced without the permission of GE.Due to technical improvements, some of the information contained in this manual may be changed without notice.© General Electric Consumer & Industrial SA. All rights reserved; reproduction without permission prohibited. The content of thismanual may be subject to change without prior notice; no liability can be accepted for any error or omission. The illustrations andplans describing the equipment are intended as general reference only and are not necessarily complete in every detail.