6.2Setting Constant ContactIDLE DOWN LIMITOPEN MODE C-STPCLOSE MODE MOMFigure 2Figure 3Figure 4Door closed -operatorstanding byCLOSE MODE C-STPFigure 5These operators are shipped from the factory with both open and closeoperating modes set to constant contact – stop (C – STP) If your unit is setto Momentary Contact (MOM) Open and/or CLOSE, reset theoperating modes by taking the following steps:1) Press CAL/RUN to enter calibration mode. Fig. 2.2) Press SET/CLEAR until display reads “OPEN MODE > C-STP.” Fig. 3.3) Press SCROLL (DN) until display reads “CLOSE MODE.” Fig. 4.4) Press SET/CLEAR until display reads “CLOSE MODE > C-STP.”Fig. 5.5) Press CAL/RUN to return to run mode.WARNING:If a monitored external reversing deviceis not used, then the operator will run Constant Contact Close.Verify close mode is set to “C-STP”and NOT “C-REV”or “MOM”before continuing.www.geniecompany.com 08-12Medium Duty OperatorGCL-MJ&MH