31-5000485 Rev. 4 15Pairing with A-coils (cont)When installers pair 14 SEER Side-discharge outdoor with a pre-existing AHU1) Ensure the 3rd party AHU is a R410a, TXV, tonnage to tonnage matched AHU2) Ensure to install a bi-flow Filter Dryer (Field supplied) in liquid line3) Ensure the lineset size matches 14 SEER Side-discharge outdoor as stated in the outdoor unit installation manual (Ifexisting lineset size is different new lineset must be installed).4) Ensure proper airflow5) Ensure existing linesets are cleaned by flushing if re-used.6) Ensure to install a bi-flow Filter Dryer (Field supplied) in gas line7) Ensure to triple evacuation the pre-existing coilIf installation guidelines and procedures are followed for each type of application above, the outdoor unit will qualify fora Limited Standard Base Warranty (i.e., 5-year parts and compressor), subject to the other limitations in the standardwarranty document.Model NumberUUC112WCDAUUC118WCDAUUC118WCDBAUUC124WCDAUUC124WCDBAUUC130WCDAUUC130WCDBAUUC136WCDAUUC136WCDBAUUC148WCDAFactory Charge Oz 49.4 75.84 81.20 97.00 100.60 116.40 119.90 123.50 127.00 141.10Liquid O.D. (Std) Inch 1/4" 1/4" 1/4" 3/8" 3/8" 3/8" 3/8" 3/8" 3/8" 3/8"Suction O.D.(Std) Inch 1/2" 1/2" 1/2" 5/8" 5/8" 5/8" 3/4" 3/4" 3/4" 3/4"Max. Refrigerant Linebetween Indoor andOutdoorFt 66 66 66 66 66 66 66 66 66 66Max. Refrigerant Lineelevation betweenIndoor and OutdoorFt 33 33 33 33 33 33 33 33 33 33Additional chargeAdditional chargeif refrigerant lineexceeding 25 ftoz/FT0.16 0.16 0.16 0.32 0.32 0.32 0.32 0.32 0.32 0.32Memo: Colored columns are paired with ADP A-coilsNote: Factory charge for UUC124WCDBA is 100.6 oz and UUC130WCDBA is 119.9 oz.INSTALLATION INSTRUCTIONS