I-7088 and M-7088 User Manual, Rev: A1.2 7MH-026-A12 1302.55. ~AATnnDescription:This command is used to set the timeout value for the software INIT.Syntax:~AATnn[CHKSUM](CR)~ Delimiter characterAA The address of the module to be set (00 to FF)T The command to set the timeout value for the softwareINIT.nn Two hexadecimal digits representing the timeout valuein seconds. The max. timeout value is 60 seconds.When changing the Baud Rate and checksum settingswithout altering the position of the INIT* pin, the ~AAIand %AANNTTCCFF commands should be sentconsecutively and the time interval between the twocommands should be less than the software INITtimeout value. If the software INIT timeout value is 0,then the Baud Rate and checksum settings cannot bechanged using software only. The power-on reset valueof the Software INIT timeout is 0.Response:Valid Command: !AA[CHKSUM](CR)InValid Command: ?AA[CHKSUM](CR)! Delimiter character for a valid command? Delimiter character for an invalid commandAA The address of the responding module (00 to FF)