7PROPERTY DAMAGE HAZARDFailure to follow this warning could result in personalinjury/death or property damage.Do not strip screws when re--securing the unit. If a screwis stripped, replace the stripped one with a larger diameterscrew (included). When straps are taut, the clevis shouldbe a minimum of 36 in. (914mm) above the unit top cover.! WARNINGRigging/Lifting of Unit1. Bend top of brackets down approximately 30 degreesfrom the corner posts.2. Attach straps of equal length to the rigging brackets atopposite ends of the unit. Be sure straps are rated tohold the weight of the unit (See Fig. 5).3. Attach a clevis of sufficient strength in the middle of thestraps. Adjust the clevis location to ensure unit is liftedlevel with the ground.4. After unit is securely in place detach rigging straps.Remove corner posts screws, and rigging bracketsthen reinstall screws.After the unit is placed on the roof curb or mounting pad,remove the top crating.FIGURE 5 Unit Corner Weight (lbs) and Riggingxy1 234Rigging Brackets are factory installed on3---phase units only. Single---phase unitsrequire accessory kit NPLIFTBK003A10CORNER WEIGHTS (SMALL CABINET) CORNER WEIGHTS (LARGE CABINET)UnitPGN324 PGN330 PGN336UnitPGN342 PGN348 PGN360lb kg lb kg lb kg lb kg lb kg lb kgTotal Weight 343 156 355 161 360 163 Total Weight 450 204 480 218 484 220Corner Weight 1 69 31 75 34 74 34 Corner Weight 1 90 41 97 44 98 45Corner Weight 2 53 24 56 25 55 25 Corner Weight 2 72 33 74 34 75 34Corner Weight 3 83 38 81 37 86 39 Corner Weight 3 110 50 116 53 118 54Corner Weight 4 138 63 143 65 145 66 Corner Weight 4 176 81 193 88 193 88Rigging Weight 353 160 365 166 370 168 Rigging Weight 465 211 495 225 499 226Shipping Weight 383 173 395 179 400 181 Shipping Weight 510 231 540 245 544 247