Jetter AG Technical specifications | 4JX3-BN-EC User Manual 11 / 864.3 Mechanical specificationsCategory Description StandardsEnclosure specificationsMaterial PlasticMaximum height of fallUnits within packing 1 m DIN EN 61131-2DIN EN 60068-2-31Units within product pack-aging0.3 mVibration resistanceFrequency sweeps 1 octave/minute,sinusoidalDIN EN 61131-2DIN EN 60068-2-6Constant amplitude 3.5 mm 5 Hz ≤ f ≤ 9 HzConstant acceleration 1 g| 9 Hz ≤ f ≤ 150 HzNumber and direction 10 sweeps for all 3 spatial axesShock resistanceType of shock Half-sine wave DIN EN 61131-2DIN EN 60068-2-27Intensity and duration 15 g for 11 msNumber and direction 3 shocks in the directions of all 3 spatial axesDegree of protectionDegree of protection IP20 DIN EN 60529Tab. 2: Mechanical specifications4.4 EMC values4.4.1 EnclosureElectrical safety Parameter Values StandardsClass of protection III DIN EN 61131-2Dielectric test voltage Functional ground is connected to chassis groundinternally.Protective connection 0Overvoltage category IITab. 3: Electrical safetyEmitted interfer-enceParameter Values StandardsFrequency band 30 … 230 MHz DIN EN 61000-6-3DIN EN 61131-2DIN EN 55011Limit value 30 dB (μV/m) at 10 mdistanceFrequency band 230 … 1,000 MHzLimit value 37 dB (μV/m) at 10 mdistanceClass BTab. 4: Emitted interferenceImmunity to inter-ferenceParameter Values StandardsMagnetic field with mains frequencyFrequency 50 Hz DIN EN 61131-2DIN EN 61000-6-2DIN EN 61000-4-8Magnetic field 30 A/m