29ID: OS27Name: Pnet_IPGatewayMeaning Indicates the actual IP Gateway of the F5 PROFINET operatorParameter number (PNU): 0198hSubindex: 0Data type: Uint32Coding: 4-byte IP-GatewayStandard value: 0.0.0.0Note: The last assigned IP Gateway adjustment by the PROFINET controller is storednon-volatile and remains active at the next start-up.From software V3.2 the val-ue of this parameter can also be written via diagnostic interface. A new value isstored non-volatile, but active only at the next switch on.ID: Fb00Name: InternComCycleMeaning Indicates whether the internal communication is cyclic or acyclic.Parameter number (PNU): 0280hSubindex: 0Data type: Uint16Coding: 0: Internal communication is acyclicOtherwise: Internal communication is cyclic with cycle time = Fb00 in μsStandard value: 0Note:ID: Fb01Name: FBS ConfigMeaning Some configuration settings of the F5 PROFINET operatorParameter number (PNU): 0281hSubindex: 0Data type: Uint16Coding: b15…b7 b6 b5 b4 b3 b2 b1 b0xxx Pnet_SubIdx_LinearEnable_PDMapUse_De-fault_PDMapPDAPI_DisableDisable_NetX_ResetSync-Mode_EnableIRT_Enablebit0 = 1 IRT_Enable: In preparationbit1 = 1 SyncMode_Enable: Enables the internal cyclic communication.bit2 = 1 Disable NetX-Reset: At fundamental problems when starting thePROFINET firmware, the CPU of the PROFINET operator can carryout a hardware reset of the PROFINET ASIC (NetX). This functioncan be disabled via this bit.further on next side