GB - 31Parameter Description6. Parameter DescriptionOn delivery the KEB COMBIVERT G6 is assigned with an user menu, the CP-Parameters.These parameters describe a selection of the most important inverter functions. If required upto maximally 48 CP-Parameters can be defined.6.1 Overview of the CP-ParametersParameter Setting Range Resolu-tion Default Unit ↵ basedonCP.0 Password input 0…9999 1 - - - ud.1CP.1 Actual frequency display -400…400 0.0125 0 Hz - ru.3CP.2 Set frequency display -400…400 0.0125 0 Hz - ru.1CP.3 Inverter status 0…255 1 0 - - ru.0CP.4 Apparent current 0…6553.5 0.1 0 A - ru.15CP.5 Apparent current peak value 0…6553.5 0.1 0 A - ru.16CP.6 Utilization 0…65535 1 0 % - ru.13CP.7 DC link voltage 0…1000 1 0 V - ru.18CP.8 DC link voltage peak value 0…1000 1 0 V - ru.19CP.9 Output voltage 0…778 1 0 V - ru.20CP.10 Minimal frequency 0…400 0.0125 0 Hz - oP.6CP.11 Maximum frequency 0…400 0.0125 70 Hz - oP.10CP.12 Acceleration time 0.00…300.00 0.01 5 s - oP.28CP.13 Deceleration time (-1=CP.12) -0.01…300.00 0.01 5 s - oP.30CP.14 S-curve time 0,00…5,00 0.01 0 s - oP.32CP.15 Boost 0.0…25.5 0.1 LTK % - uF.1CP.16 Rated frequency 0…400 0.0125 50 Hz - uF.0CP.17 Voltage stabilization 0…649 V, oFF 1 off V E uF.9CP.18 Switching frequency 0…LTK 1 LTK - E uF.11CP.19 Fixed frequency 1 -400…400 0.0125 5 Hz - op.21CP.20 Fixed frequency 2 -400…400 0.0125 50 Hz - op.22CP.21 Fixed frequency 3 -400…400 0.0125 70 Hz - op.23CP.22 DC braking mode 0…9 1 7 - E Pn.28CP.23 DC braking time 0.00…100.00 0.01 10 s - Pn.30CP.24 Max. ramp current 0…200 1 140 % - Pn.24CP.25 Max. constant current 0…200 1 200:off % - Pn.20CP.26 Speed search condition 0…15 1 8 - E Pn.26CP.27 Motor protection response 0…6 1 6 – – Pn.14CP.28 Motor protection mode 0…1 1 1 – – dr.11CP.29 Motor protection rated current 0.0…370.0 0.1 LTK A – dr.12CP.30 Analog output function 0…26 1 2 – E an.31CP.31 Analog output amplification -20.00…20.00 0.01 1 – – an.33CP.32 Transistor output function 0…86 1 20 – E do.00CP.33 Relay output function 0…86 1 4 – E do.02CP.34 Relay output switching level ±30000.00 0.01 100.00 – – Le.02CP.35 Set value selection 0…2 1 0 – E An.00CP.36 Select 50/60Hz mode 0…1 1 0 – E ud.06CP.37 Response to external overtemperature 0…7 1 7 - - Pn.12LTK=depending on power unit; E=ENTER parameter1) The CP-Parameter group is a selection of more than 500 parameters and 8 parametersets for simple applications. Each CP-Parameter (not CP.00) can be individually assigned soa special final customer menue is generated. Further documentation is specified at the endof this manual.