172.2 Technical Data 460V ClassTechnical Data1) The wire gauge is based on the maximum fuse rating, copper wire with minimum 75°C insulation rating, THHW or equivalent.If branch circuit protection is selected based on rated input current, the wire size could be reduced.2) With the regulated systems F5-M as well as F5-S 5% must be subtracted as control reserve3) Rated operation means, rated input voltage, rated output current, and rated carrier frequency.4) This data is only valid for units with internal brake transistor GTR 7 (see "unit identification")5) With units with integrated EMI filter the distance is less:up to max. 5m line length and 4kHz operating frequency = Limit Value B (EN 55011)up to max. 10m line length and 16kHz operating frequency = Limit Value A (EN 55022)Inverter Size 05 07 09 10 12 13 14Recommended Motor Power [hp] 1/2 1 2 3 5 7,5 10Housing size B B B D B D B D E D E G D E GInput RatingsSupply voltage [V] 305...500 ±0 (460 V Nominal voltage 4) )Supply voltage frequency [Hz] 50 / 60 +/- 2Input phases 3 3 3 3 3 3 3Rated input current [A] 1,4 2,5 4,8 6,7 11 15 20Recommended maximum input fuse [A] 15 15 15 15 20 25Recommended wire gauge1) [awg] 14 14 14 14 12 10Output RatingsRated output power [kVA] 0,9 1.8 2,8 4.0 6.6 8.3 11Rated motor power [kW] 0,37 0.75 1,5 2,2 4.0 5.5 7,5Rated output current [A] 1.0 1.8 3.4 4.8 7.6 11 14Peak current (30 seconds)2) [A] 2.3 4.7 7.4 10.4 17 18 29,7 24,8Over current fault (E.OC) trip level [A] 2.8 5.6 8.9 12.5 21 21.6 35,6 29,7Overload curve (see annex) 1Output voltage [V] 3 x 0…V LineOutput frequency [Hz] Generally 1600Hz however it is limited by the switching frequencyRated switching frequency [kHz] 16 16 8 8 8 16 4 8 16 4 8 16 2 8 16Maximum switching frequency [kHz] 16 16 16 16 16 16 4 16 16 16 16 16 4 16 16Power loss at rated operation3) [W] 60 90 80 105 120 170 150 185 300 185 250 200 185 320 260Stall current at 4kHz [A] 1,3 2,6 4,1 4,1 5,8 5,8 7,6 9,5 9,5 12 12 12 14 16,5 16,5Stall current at 8kHz [A] 1,3 2,6 4,1 4,1 5,8 5,8 – 9,5 9,5 9,5 12 12 - 16,5 16,5Stall current at 16kHz [A] 1,3 2,6 3,5 3,5 4,9 5,8 – 5,8 9,5 5,8 12 12 - 10 12Braking CircuitMin. braking resistance 4) [Ohm] 390 120 120 82 82 56 39 50Typ. braking resistance 4) [Ohm] 390 390 270 270 150 100 82Max. braking current [A] 2.2 7.5 7.5 10 10 15 21 15Installation InformationMax. shielded motor cable length at 4 kHz 5) [ft 30 30 330 330 330 165 330 300 300Max. shielded motor cable length at 8 kHz 5) [ft 25 25 100 165 330 – 330 300 - 330Max. shielded motor cable length at 16kHz5) [ft 15 20 100 100 65 – 330 300 - 330Tightening torque for terminal strip [in lb] 4.5 4.5 4.5 11 4.5 4.5 11EnvironmentalMax. heat sink temperature TOH [°C] 90°C / 194°FStorage temperature [°C] -25...70 °C / -13…158°FOperating temperature [°C] -10...45 °C / 14…113°FHousing design / protection Chassis / IP20Relative humidity max. 95% without condensationApprovalsTested in accordance with… EN 61800-3 /UL508CStandards for emitted interference EN 55011 Class B / EN 55022 Class AStandards for noise immunity IEC 1000-4-2 / -3 / -4 / -5/ -6Climatic category 3K3 in accordance with EN 501782012392121.625.9