LAARS’ ProtoNode Startup GuideAppendix A.4. BACnet: Setting Network_Number for more than one ProtoNode on SubnetFor both BACnet MS/TP and BACnet/IP, if more than one ProtoNode is connected to the same subnet,they must be assigned unique Network_Number values.On the main Web Configuration screen, update the Network Number with the “network_nr” field and clicksubmit. The default value is 50.There is a Network number field for BACnet/IP and a Network number field for BACnet MS/TP, please fillin the appropriate box.Figure 26: Web Configurator showing setting the network number for BACnetThe LAARS Gateway LER and RER Startup GuidePage 33 of 4320 Industrial Way, Rochester, NH, USA 03867 • (800) 900-9276 • www.Laars.com 1604 Document 4236E