334 Commissioning/DecommissioningThe condition ’inactive’ is displayed, if the limit value is not set in the parameter or if thelimit value is deactivated by the digital inputs or the operating mode (parameter 967).• All limit values can be deactivated together depending on the operating mode.The behaviour can be set in parameter 967 in service level.Parameter values: 0 = never, 1 = cold start (default), 2 = cold start + maintenance, 3 = nomeasurement.Faults and warnings have no influence of the limit values!• Each limit value can be deactivated by the function ’Deakt. GWx by the digital inputs(x={1,2,3,4}).4.4.10 Display of the Limit Value CrossingFig. 4-11 Display LT2 limit valuesThe limit values are displayed by means of the soft-keys.When limit value parameters 930/940/950/960 are activated in the access level ’Service’, thedisplay shows Li1, Li2, Li3 and Li4 depending on the currently activated limit value.Exceeding the limit values:Li 1 = Li1 has been exceeded (higher than limit value)Li 2 = Li2 has been exceeded (lower than limit value)