RE72-09B User’s Manual 46Input ranges Table 17Kind of sensorsRangeUNIT = °C[x10]UNIT = °F[x10] UNIT = PUPt100 -2000…………8500 -3280…………15620Pt1000 -2000…………8500 -3280…………15620Fe-CuNi (J) -1000…………12000 -1480…………21920Cu-CuNi (T) -1000…………4000 -1480…………7520NiCr-NiAl (K) -1000…………13720 -1480…………25016PtRh10-Pt (S) 0…………17670 320…………32126PtRh13-Pt (R) 0…………17670 320…………32126PtRh30-PtRh6 (B) 0…………17670 320…………32126NiCr-CuNi (E) -1000…………10000 -1480…………18320NiCrSi-NiSi (N) -1000…………13000 -1480…………23720chromel – kopel (L) -1000…………8000 -1480…………14720Linear current (I) -1999…………9999Linear current (I) -1999…………9999Linear voltage (U) -1999…………9999Linear voltage (U) -1999…………999915. SOFTWARE UPDATINGFunction enabling updating of software from the computer of the PC with software LPCon wasimplemented in controller RE72 (from version of software 2.00). Free software LPCon and update filesare available at www.lumel.com.pl. The connected to the computer convertor RS485 is required onUSB to the updating, e.g.: the convertor PD10.a) b)Fig.28. Program view: a) LPCon, b) updating of softwareWarning! Before doing update, currently settings of controller should be saved by program LPCon,because when software is updated default settings of controller are restored.After starting LPCon's software COM port, baudrate, transmission mode and adress should be set. Itcan be done in Options. Then, RE72 controller should be selected from Device. Push icon Load toAutomatización IndustrialTelf.: 423-5567 / 711-9345 - RPM.: #981156320 / *975084 / #999976999 E-mail.: ventas.1@csrimport.com / www.csrimport.comAutomatización Industrial