N° Default value & other possibilities02 XX.X : Calibration of the Internal ProbeThe calibration must be done after 1 day working with the same setting temperature inaccordance with the following description:Put a thermometer in the room at 1.5m distance from the floor (like the thermostat) andcheck the real temperature in the room after 1 hour.When you enter the calibration parameter screen the actual temperature value isdisplayed.To enter the value shown on the thermometer, use the “-“ or “+” keys to enter the realvalue. At this point the hand icon, in section 12 of the LCD display, will bedisplayed and the value will blink. Press the “OK” key to confirm and save. If you needto erase a calibration already saved use the “-“ or “+” keys to alter the value,even just by 1°C , then press the left “” navigation key. The hand symbol willdisappear and the factory calibrated temperature reading will be displayed.NOTE: Only the heating elements (including slave radiators) managed by thethermostat must be used during the calibration process. Do not have a secondaryheat source in the same room for a period of 24 hours before hand.11.0 Parameter’s Menu (cont...)11.0 Parameter’s Menu (cont...)17RIORIO1603 SrC : Sequential Control of Front and Back PanelNOTE: This feature is only applicable to double panel radiators.Press “OK” to enter this parameter. Select with “+” or “-”and confirm by pressing the“OK” key:no: Sequential control function disabled (Front=Back).YES: Sequential control function enabled. Heat output is prioritised to the front panel tomaximise radiant heat. Thus, the “back” heating element will activate if thetemperature is one degree below the set point, acting as a booster.NOTE: The rear panel temperature can be considerably lower than the front panelwhen this function is enabled.04 Software VersionDisplays the software version of the digital thermostat.N° Default value & other possibilities06 ItCS : Adaptive StartPress the “OK” key to enter this parameter. Select with “+” or “-” and confirm byopressing the “OK” key:no: adaptive start function disabled. Heating up to reach the Comfort set temperaturewill start at the programmed time.YES: adaptive start function enabled. Heating up will start at the predicted optimal timeto reach the Comfort set temperature at the programmed time.NOTE: Heating start times will vary for each heating period when this functionis enabled.07 SLA : Master/Slave Set-upSet this function to ‘no’ for normal operation.05 Wind : Open Window Detection(the text “U–ind” is displayed)Press the “OK” key to enter this parameter. Select with “+” or “-” and confirm byopressing the “OK” key:no: open window detection function disabled.YES: open window detection function enabled. The , in section 13 of the LCDdisplay, is constantly displayed. This function will switch the radiator from any activemode to “Frost Protection” mode when an open window is detected (roomtemperature drops within a certain time). The open window icon will start to blink,and continue to blink as long as the function is active.To return to the previous or automatic mode, press the “OK” key twice. If theradiator detects that the window has been closed (room temperature increaseswithin a certain time), it will return automatically to the previous or automaticoperation mode.