12 / 24 pmg4111a0600p_017.5 C ONFIGURATION MODE7.5.1 MODE S ETTINGSNormal (measurement) modeMode settings3 s3 s+PROGRAMMING SEQUENCE Select the input from 19 options Select alarm relay mode Select alarm output mode. Select auto-tuning mode Select PID control algorithm Select cooling or heating control Select temperature measurement unit Setting the high limit scale value of the analogue input Setting the low limit scale value of the analogue input Setting the decimal point (only in case of analogue input) Turning on or off the RAMP function Turning on or off the Key lockIn normal (measurement) mode press the and the buttons and hold for 3 secondsto change the mode settings. If the configuration is completed press the button andhold for 3 seconds to return to normal (measurement) mode.The (decimal point setting) menu item appears only if analogue output is used. Alsothe , , options only appears in the (input selection) list if properjumper settings are made as described in chapter 5.1 „Input”.