pmg4111a0600p_01 17 / 249.1.1 A NALOGUE INPUTWhen using analogue input the UNICONT controller could be connected to a 4-20 mA output leveltransmitter device for example.Scaling:In case of temperature measurement if the input is Pt100 or thermocouple, the device automaticallydetermines the measurement range and the position of the decimal point according to the selected type ofthe input signal.When analogue input is used (4-20 mA, 0-10 V DC, 1-5 V DC) low and high limit values should bespecified for the input measurement range. These values can be entered in the and modesettings. In addition you can set the decimal point location at the mode setting.Application example:Controlled device(e.g. pump)Level meter(e.g. EasyTREK SPA-380-4Ultrasonic level transmitter)Analogue output(e.g. 4-20 mA)(input mode): (4-20 mA) (measurement range high level): (mm)(measurement range low level): (mm) (position of the decimal point): Note:For using analogue input proper jumper settings are required as described in chapter 5.1 „Input”.