11Filling the condensate trap with waterThe condensate trap can be ¿lled before connecting the vent pipe.Filling the condensate trap before vent pipe installation.DANGER Prior to initial start up, make sure that you ¿ll the condensate trap with water.This is to prevent dangerous exhaust gases from entering the building.Failure to ¿ll the condensate trap could result in severe personal injury or death.Please follow one of the procedures described below to ensure that the condensate trap is ¿lled with water.1) Fill the condensate trap by pouring approx. 30 oz.(850ml) of water into the exhaust accessory on the topof the appliance as illustrated below.Or, if the vent pipe has already been installed:2) After installing the drain pipe, make sure that the area around the appliance is well ventilated; open awindow or a door if necessary.Then, operate the unit and verify that condensate is coming out of the drain pipe.(During normal use of the water heater, condensate will begin to discharge from the drain pipe within15 minutes of use. However, depending on the season and/or installation site conditions, it may take longer.)Note: The condensate discharged from the water heater has a pH level of approximately 2-3.If required by local code, the condensate must be neutralized prior to disposal into the sewer system.Refer to pages 25-26 for additional details.30 oz.850mlIntakeExhaust