User’s Manual Rev1.0Date:15/07/2015 User’s Manual22/475.2 Setting listPlease check chart 5.1 and 5.2 for code and digital setting address list.Chart 5.1 Code setting addressCode settingaddress Item Code Description of codeC01 Start up time 01~99 Set the start up time within 1~99 secondsC02 Density type00 Display standard volume flow rate01 Density preset, display mass flow02 Display actual flow rateC03 Pulse output type00 pulse output off01 Frequency output02 Pulse equivalent outputC06 Pulse outputparameter00 Flow rate01 Temperature02 Pressure03 Total flowC07 Damping 01~16 1~16 secondsC08 Instrument number00~99 For Modbus00~15 For HART communicationC09 Baud rate1 1200 no parity 1 stop bit2 1200 even parity 1 stop bit3 2400 no parity 1 stop bit4 2400 even parity 1 stop bit5 4800 no parity 1 stop bit6 4800 even parity 1 stop bit7 9600 no parity 1 stop bit8 9600 even parity 1 stop bit9 19200 no parity 1 stop bit10 19200 even parity 1 stop bit11 1200 odd parity 1 stop bit12 2400 odd parity 1 stop bit13 4800 odd parity 1 stop bit14 9600 odd parity 1 stop bit15 19200 odd parity 1 stop bit16 38400 no parity 1 stop bit17 38400 even parity 1 stop bit18 38400 odd parity 1 stop bit19 57600 no parity 1 stop bit20 57600 even parity 1 stop bit21 57600 odd parity 1 stop bit22 115200 no parity 1 stop bit23 115200 even parity 1 stop bit24 115200 odd parity 1 stop bit