Installation3-6P/N 7105144G 2008 Nordson CorporationVersaBlue_NWElectrical ConnectionsWARNING: Risk of electrical shock. Failure to observe may result inpersonal injury, death, or equipment damage.Important Note When Using Residual Current Circuit BreakersLocal regulations in some geographic areas or industrial branches mayrequire residual current circuit breakers.Then observe the following points: Residual current circuit breakers are to be installed only between thepower supply and the melter. Only residual current circuit breakers sensitive to pulsating current oruniversal current (> 30 mA) may be used.Laying CableWARNING: Use only temperature resistant cable in warm areas of theequipment. Ensure that cables do not touch rotating and/or hot meltercomponents. Do not pinch cables and check regularly for damage. Replacedamaged cables immediately!CAUTION: Lay CAN bus cable with a bending radius > 60 mm (2.4 in).Operating VoltageWARNING: Operate only at the operating voltage shown on the ID plate.NOTE: Permitted deviation from the rated line voltage is 10%.NOTE: The power connection cable must have a cross-section appropriatefor the maximum power consumption (refer to section Technical Data).External Control/Signal CircuitsWARNING: Connect external control and signal circuits with suitable cablein accordance with the NEC, class 1. To prevent short-circuiting, lay thecables such that they do not touch printed circuits on PCBs.