OutputsInputsInstallation3-12P/N 7105144G 2008 Nordson CorporationVersaBlue_NWInterface AssignmentInterface Standard I/O − Standard Assignment −General Notes To conform with a European standard regarding electro-magneticcompatibility (EMC), only shielded cable may be connected. The cablemust be connected to ground in compliance with the standard regardingelectromagnetic compatibility. Inductive loads (e.g. solenoid valves) connected to the melter must beequipped with a protective device (e.g. recovery diode) that disables theinductive voltage generated when an inductive load is switched off. The permitted voltage deviation is 10%. In Field bus mode (option Fieldbus communication) the unit can not becontrolled via the interface.Digital inputsPin Input Function1* 24 VDC Internal (melter)2* 0 VDC External (customer’s)NOTE: Customer connects his reference potential here, if 24 VDC is provided bycustomer.3 0 V24 V Rising edge: Heaters ON (main contactor closes)0 V24 V Falling edge: Heaters OFF (main contactor opens)4 24 V: All motors ON (collective enable)0 V: All motors OFF5 24 V: Enable Motor 10 V: No Motor 1 enable6 24 V: Enable Motor 20 V: No Motor 2 enable7 24 V: Enable Motor 30 V: No Motor 3 enable8 24 V: Enable Motor 40 V: No Motor 4 enable9 0 V24 V Rising edge: Switch on Standby0 V24 V Falling edge: Switch off Standby10 0 V24 V Rising edge: Key-to-line mode (for all motors)0 V24 V Falling edge: Manual mode (for all motors)* selectable