4810. Water PipingThis appliance is suitable for potable water and space heating applications. Do not use this appliance if any part hasbeen underwater. Immediately call a qualified service technician to inspect the appliance and replace any part of thecontrol system and gas control which has been under water.If the water heater is installed in a closed water supply system, such as one having a backflow preventer in the coldwater supply line, means shall be provided to control thermal expansion. Contact the water supplier or a local plumb-ing inspector on how to control this situation.A pressure relief valve must be installed near the hot water outlet that is rated in accordance with and complying witheither The Standard for Relief Valves and Automatic Shutoff Devices for Hot Water Supply Systems, ANSI Z21.22, orThe ANSI/ASME Boiler and Pressure Vessel Code, Section IV ( Heating Boilers ). This pressure relief valve mustbe capable of an hourly Btu rated temperature steam discharge of 194,000 Btuh. Multiple valves may be used. Thepressure relief capacity must not exceed 150 psig. No valve shall be placed between the relief valve and the waterheater. The relief valve must be installed such that the discharge will be conducted to a suitable place for disposalwhen relief occurs. No reducing coupling or other restriction may be installed in the discharge line. The discharge linemust be installed to allow complete drainage of both the valve and the line. If this unit is installed with a separatestorage vessel, the separate vessel must have its own temperature and pressure relief valve. This valve must alsocomply with The Standard for Relief Valves and Automatic Gas Shutoff Devices for Hot Water Supply Systems, ANSIZ21.22. (in the U.S. only). A temperature relief valve is not required, but if one is used, do not install the valve with theprobe directly in the flow of water. This may cause unwarranted discharge of the valve.Piping and components connected to the water heater shall be suitable for use with potable water.Toxic chemicals, such as those used for boiler treatment, shall not be introduced into the potable water.A water heater used to supply potable water may not be connected to any heating system or components previouslyused with a nonpotable water heating appliance.When water is required in one part of the system at a higher temperature than in the rest of the system, means suchas a mixing valve shall be installed to temper the water to reduce the scald hazard.• Flush water through the pipe to clean out metal powder, sand and dirt before connecting it.• Take appropriate heat insulation measures (e.g., wrapping with heat insulation materials, using electric heaters)according to the climate of the region to prevent the pipe from freezing.• Use a union coupling or flexible pipe for connecting the pipes to reduce the force applied to the piping.• Do not use piping with a diameter smaller than the coupling.• When feed water pressure is too high, insert a depressurizing valve, or take water hammer prevention measures.• Avoid using joints as much as possible to keep the piping simple.• Avoid piping in which an air holdup can occur.• Use approved piping materials.• If installing the unit on a roof:If the unit is installed on a roof to supply water to the levels below, make sure that the water pressure supplied tothe unit does not drop below 29 psi. It may be necessary to install a pump system to ensure that the water pressureis maintained at this level.Check the pressure before putting the unit into operation.Failing to supply the proper pressure to the unit may result in noisy operation, shorter lifetime of the unit, andmay cause the unit to shut down frequently.Supply water piping• Do not use PVC piping.• Mount a check valve and a shut off valve (nearthe inlet).• In order for the client to use the water heatercomfortably, 98.1 to 491 kPa (14 to 70 PSI) ofpressure is needed from the water supply.Be sure to check the water pressure. If the waterpressure is low, the water heater cannot performto its full capability, and may become a source oftrouble for the client.Drain piping• Expansion water may drop from the pressureprevention device and wet the floor. If neces-sary, provide drain piping or use a drain hose toremove the water.Hot water piping• Do not use lead or PVC piping.• The longer the piping, the greater the heat loss.Try to make the piping as short as possible.• Use mixing valve with a low water resistance.Use shower heads with low pressure loss.• If necessary, use a pump or other means to en-sure that the supply water pressure to the inletof the heater does not fall below 29 PSI whenthe maximum amount of water is being de-manded. Also install a pressure meter on the in-let. If this is not done, local boiling will occur in-side the water heater causing abnormal soundsand decreasing the durability of the heat ex-changer.Ask a qualified plumber to perform the installationof the plumbing. Observe all applicable codes.