3GQuick ConnectCordRemote Controller Cord Gas Supply PipingCold Water SupplyHot WaterRemote ControllerTerminal BlockCordConnectorCordConnector3. Quick Connect Multi System Installation• The Quick Connect Multi System allows the installation of two units together utilizing only the QuickConnect Cord.Typical PlumbingThe Quick Connect Cord is 2m (6'). long. Install the units 50 - 450mm (2-18") apart from eachother to ensure the cord will be able to reach between the units. (See Typical Plumbing diagram).(If the distance between the two units is too great, not only will the cord not be able to reach,but the water temperature may also become unstable because of the difference in pipe lengthbetween the two units).* When connecting two units, use onlya single remote controller.Note: Connect the remotecontroller to only oneof the units.System Diagram• Insulate the hot water piping to prevent heat loss. Insulate and apply heating materials to the coldwater supply piping to prevent heat loss and freezing of pipes when exposed to excessively coldtemperatures.Distance at center400 - 800mm (16-32")Distance on sides50 - 450mm (2-18")UnionMake this distance as short as possible.* The hot water temperature willbecome unstable as the pipelength increases.Quick ConnectcordUnionGas ValveUnionShutoffValve Shutoff ValveHot WaterCold WaterShutoffValveLeave enough clearance around the plumbing toapply insulation. It will be necessary to addbends to the piping to ensure that this clearanceis available.PressureReliefValveSize the piping to allow for the maximumflow rates of the units.