CPC 100 V1.415 - 24Automatic Test vs. Manual Test1. Option "Manual input" clearAutomatic test– Press the I/O (test start/stop) push-button to start the test.The test voltage increases from 0V to Vtest in a ramp characteristic within1 second. Then Vtest is kept for a period of 2.4 seconds, and themeasurements are taken. Next, the ramp decreases again within0.3 seconds.– The automatic test stops by itself, it can now be assessed.– To repeat the test, first press B A C K T O T O P , if applicable, and then C L E A RR E S U L T S .Manual testClearing "Auto" lets you set the test voltage Vtest manually with the handwheel.– Press the I/O (test start/stop) push-button to start the test. The focus is setonto the "V test:" entry field.– Set the value of your choice either by turning the handwheel and/or byentering it with the numerical keys.– Now the measurements are taken and displayed.– To save the measurement press K E E P R E S U L T S (pressing the I/O push-button has the same effect). The last measured values are "frozen", the testcan now be assessed.– Stop the manual test by pressing the I/O (test start/stop).– To repeat the test, first press B A C K T O T O P , if applicable, and then C L E A RR E S U L T S .Note: A value set with the numerical keys needs to be fully entered andacknowledged by pressing either E N T E R or the handwheel beforeit is applied to the output. If needed, it can then be adjusted usingthe handwheel.Values set by turning the handwheel are applied instantaneously.