6.3 Setting Items for PLC Link6-96.3.5 Starting No. for Link Relay Send Area and Sending Size The memory areas for link relays are divided into send areas and receive areas. The link relays are transmitted from the send area to the receive area of a different PLC.Link relays with the same numbers as those on the sending side must exist in the receivearea on the receiving side.E.g. Example of setting the starting No. for link relay send area and the sending size (inthe case of memory block No.0) List of setting items (PLC link settings)Station no. and setting methodSetting items Settingrange No.1 No.2 No.3 No.4Memory block numbers for linkrelays and link registers to beused0 or 1 0 0 0 0Maximum station no. to be usedfor PLC link 0 to 16 4 4 4 4Range of link relays used 0 to 64words 64 64 64 64Starting no. for link relay sendarea0 to 63 0 20 40 0Size of link relay send area 0 to 64words 20 20 24 0Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com