8-78.3 PID control sample program- PID controlWhen a K-type thermocouple is connected with the thermocouple input of FP-e, PIDtemperature control can be easily conducted. (In addition, parameter setting can beautomatically selected using “AUTO TUNING.”)- Thermocouple input specificationsItem DescriptionNumber of input point 2 points (CH0: WX1, CH1: WX2)Temperature sensor type K-type thermocoupleInput temperature range - 30.0 to 300.0 ºC (- 22 to 572 °F)Accuracy ±0.5 %FS±1.5 ºC (FS = - 30 to 300 ºC)Resolution 0.1 ºCConversion time 250 ms/2CHInsulation method Between internal circuit and thermocouple input circuit: noninsulatedBetween CH0 and CH1 of thermocouple input: PhotoMos insulationDetection function ofwire disconnection AvailableReference: Description of the specifications <2.3.1 Input specifications>- ThermocoupleA thermocouple is the sensor that measures the temperature using the thermo-electromotive force generated by the temperature difference between two metal wiresconnected, whose materials are different.Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com