3712.5. Timer Control• There are 2 sets of ON and OFF timer available to turn the unit ON or OFF at different preset time.• If more than one timer had been set, the upcoming timer will be displayed and will activate in sequence.12.5.1. ON Timer ControlON Timer 1 and ON Timer 2 can be set using remote control, the unit with timer set will start operate earlier than the setting time.This is to provide a comfortable environment when reaching the set ON time.60 minutes before the set time, indoor (at fan speed of Lo-) and outdoor fan motor start operate for 30 seconds to determine theindoor intake air temperature and outdoor air temperature in order to judge the operation starting time.From the above judgment, the decided operation will start operate earlier than the set time as shown below.12.5.2. OFF Timer ControlOFF Timer 1 and OFF Timer 2 can be set using remote control, the unit with timer set will stop operate at set time.12.6. Auto Restart Control1. When the power supply is cut off during the operation of air conditioner, the compressor will re-operate within three to fourminutes (there are 10 patterns between 2 minutes 58 seconds and 3 minutes 52 seconds to be selected randomly) afterpower supply resumes.2. This type of control is not applicable during ON/OFF Timer setting.12.7. Indication PanelNote:• If POWER LED is blinking, the possible operation of the unit are Hot Start, during Deice operation, operation mode judgment, orON timer sampling.• If Timer LED is blinking, there is an abnormality operation occurs.• If e-ion LED is blinking, there is an abnormality of e-ion occurs.• If PATROL LED is blinking, there is a gas sensor error detection.LED POWER TIMER QUIET POWERFUL e-ion ECO PATROL PATROL SENSORColor Green Orange Orange Orange Blue Green BlueLight ON Operation ON Timer Setting ON Quiet Mode ON Powerful Mode ON e-ion ON Eco Patrol ON Patrol ONLight OFF Operation OFF Timer Setting OFF Quiet Mode OFF Powerful Mode OFF e-ion OFF Eco Patrol OFF Patrol OFF