8.2.1. SELECT THE BEST LOCATION(Refer to “Select the best location”section)8.2.2. HOW TO FIX INSTALLATIONPLATEThe mounting wall is strong and solid enough to prevent it fromthe vibration.The centre of installation plate should be at more than 450 mmat right and left of the wall.The distance from installation plate edge to ceiling should morethan 67 mm.From installation plate left edge to unit’s left side is 47 mm.From installation plate right edge to unit’s right is 73 mm.:::For left side piping, piping connection for liquid should beabout 14 mm from this line.For left side piping, piping connection for gas should beabout 56 mm from this line.For left side piping, piping connecting cable should beabout 785 mm from this line.1. Mount the installation plate on the wall with 5 screws ormore.(If mounting the unit on the concrete wall consider usinganchor bolts.)•••• Always mount the installation plate horizontally byaligning the marking-off line with the thread and using alevel gauge.2. Drill the piping plate hole with ø70 mm hole-core drill.•••• Line according to the arrows marked on the lower leftand right side of the installation plate. The meeting pointof the extended line is the centre of the hole. Anothermethod is by putting measuring tape at position asshown in the diagram above. The hole centre isobtained by measuring the distance namely 150 mmand 125 mm for left and right hole respectively.•••• Drill the piping hole at either the right or the left and thehole should be slightly slanted to the outdoor side.8.2.3. TO DRILL A HOLE IN THE WALLAND INSTALL A SLEEVE OFPIPING1. Insert the piping sleeve to the hole.2. Fix the bushing to the sleeve.3. Cut the sleeve until it extrudes about 15 mm from the wall.CautionWhen the wall is hollow, please be sure to use thesleeve for tube ass’y to prevent dangers caused bymice biting the connecting cable.4. Finish by sealing the sleeve with putty or caulkingcompound at the final stage.8.2.4. INDOOR UNIT INSTALLATION1. For the right rear piping2. For the right and right bottom piping8.2. INDOOR UNIT30CS-PW9CKE / CU-PW9CKE / CS-PW12CKE / CU-PW12CKEPanasonic ilmalämpöpumput korjaa ja huoltaa pääkaupunkiseudulla: Jäähdytinpalvelu RefGroup Oywww.ilmalämpöpumput.com