2512. Operation Control12.1 Basic Function12.1.1 Internal Setting TemperatureOnce the operation starts, remote control setting temperature will be taken as base value for temperature shiftingprocesses. These shifting processes are depending on the air conditioner settings and the operation environment.The final shifted value will be used as internal setting temperature and it is updated continuously whenever theelectrical power is supplied to the unit.12.1.2 Cooling Operation12.1.2.1 Thermostat control• Compressor is OFF when Intake Air Temperature - Internal Setting Temperature < -1.5℃• Compressor is ON after waiting for 3 minutes, if the Intake Air Temperature - Internal Setting Temperature >Compressor OFF point +0.5K.12.1.3 Soft Dry Operation12.1.3.1 Thermostat control• Compressor is OFF when Intake Air Temperature - Internal Setting Temperature < -2.5℃• Compressor is ON after waiting for 3 minutes, if the Intake Air Temperature - Internal Setting Temperature >Compressor OFF point +0.5K.Remote Control Setting Temp. (16℃~30℃)Auto operation Mode ShiftingInternal Setting TemperatureSetting Temperature Limit Checking (Min.:16℃~Max.:30℃)Powerful Temperature ShiftingFan speed ShiftingDry mode ShiftingCooling/Heating ShiftingSetting Temperature Limit Checking(Min: 16℃; Max.: 33℃)