8.4. Automatic Mode Operation1. When the Automatic Mode Operation is selected, the indoor fan operates at SLo fan speed for 25 seconds to sense intake airtemperature and determine the 1st operation mode.2. Operation mode will be determine again after 1 hour of operation, if the room temperature reaches to set temperature andcompressor off time is over 7 minutes 30 seconds continuously.The present operation mode will be continued, if the room temperature does not reach to set temperature (Compressor keeps running)eventhough after 1 hour from automatic operation mode started.Present Judgement Next ModeMode Cooling Soft Dry HeatingO OCooling 23°C Cooling (Judgement: Not Applicable (Judgement:Heating 23°C & Above) Below 23°C)O OSoft Dry 20°C Soft Dry Not Applicable (Judgement: (Judgement:Heating 20°C & Above) Below 20°C)O OHeating Cooling (Judgement: Not Applicable (Judgement:25°C Heating Above 25°C) 25°C & below)Automatic Set TemperatureRefer 3. as below.3. Automatic Set TemperatureFor each operation, set temperature will automatically set as shown below.However it can be selected 2°C higher or 2°C lower from standard set temperature by pressing the “Room Temperature Settingbutton”.Operation Hi (Standard) Lo(+2°C) (±0°C) (-2°C)Cooling 27°C 25°C 23°CSoft Dry 24°C 22°C 20°CHeating 23°C 21°C 19°C• The mode judging temperature and standard setting temperature can be increased by 2°C, by open the circuit of JX1 atindoor electronic controller.29CS-W7CKP CU-W7CKP5 / CS-W9CKP CU-W9CKP5 / CS-W12CKP CU-W12CKP5Panasonic ilmalämpöpumput korjaa ja huoltaa pääkaupunkiseudulla: Jäähdytinpalvelu RefGroup Oywww.ilmalämpöpumput.com