5813.15 Valve close detection control This control detects 3-way valve close condition to prevent damage to refrigerant cycle. Start conditions:o For all connected indoor units, if Indoor intake temperature — indoor piping temperature are between 28.4°F(-2°C) and 35.6°F (2°C) continuously for 5 minutes after compressor ON at first cooling operation.o The first cooling operation is defined as cooling operation is ON for less than 8 minutes after new installationor after pump down. Control contento During this control, compressor stop, indoor units’ Timer LED will blink. (“F91” is indicated at indoor units) Error reset can be done by power supply reset or reset by using remote control.13.16 Compressor discharge high pressure protection control This control protect by using high pressure switch during operation. Start conditionso High pressure switch is activated (from normally close to open) when outdoor operation mode is cooling orheating during compressor running. Control 1 contento Compressor stop when high pressure switch is opened and restart after high pressure switch closed. If thiscondition happen 4 times within 30 minutes, “F94” is indicated.o After 30 minutes, counter is reset if this condition does not happen for 4 times. Control 1 stop conditionso Power supply reseto Reset by using remote control13.17 Compressor Heater control Specification:o Power: 30 Watto Voltage: 240 Volt Purpose:o To control compressor crankcase heater operation to melt ice on compressor during heating operation Starting conditions:o When outdoor air temperature ≤ 4°C (39°F) and compressor top temperature ≤ 21°C (70°F) Control contents:o Power supply to compressor heater is ON Cancel conditions:o When outdoor air temperature exceeds by 6°C (43°F) oro When compressor top temperature exceeds 26°C (79°F)