6515.2 Self-diagnosis Method15.2.1 H11 (Indoor/Outdoor Abnormal Communication)Malfunction Decision Conditions During standby and operation of cooling and heating, the data received from outdoor unit in indoor unit signaltransmission is checked whether it is normal.Malfunction Caused Faulty outdoor unit PCB. Faulty indoor unit PCB. Indoor-outdoor signal transmission error due to wrong wiring. Indoor-outdoor signal transmission error due to breaking of wire in the connection wires between the indoor andoutdoor units. Indoor-outdoor signal transmission error due to disturbed power supply waveform.Abnormality Judgment: After operation for 1 minute.TroubleshootingCheck the indoor-outdoorunits connection wires.Correct the indoor-outdoorunits connection wires.Is there any wiring error?Disconnect terminal 3wire and measure Vdcbetween terminal 2 & 3from the outdoor unit.Is the Vdc fluctuatebetween 10-70Vdc?Reconnect terminal 3wire and measure Vdcbetween terminal 2 & 3from the outdoor unit.Is the Vdc fluctuatebetween 10-70Vdc?Replace outdoor unitPCB.YesReplace indoor unit PCB.For safety reason and to prevent componentbreakdown, always switch off the power beforeremove and connect the component.YesNoNoNoYesCaution