11(EN)Switches*The factory defaults are as follows.OFF : SW1·2·3·4·8ON : SW5·6·7[SW1•2] Zone address settingSelect a zone from Zone 1 to 4 based on the group (Central address) to operate.[SW3] ON/OFF controller Main/Sub setting (Main: OFF Sub: ON) When installing one ON/OFF controller in one zone, set this to Main (OFF). When installing two ON/OFF controllers in one zone, set one to Main (OFF) and the other to Sub (ON). Up to two ON/OFF controllers with Main and Sub combined can be connected for each zone.Zone 1Group 1 to 16⾷SW1⿉OFFƷSW2⿉OFF⾸Zone 2Group 17 to 32⾷SW1⿉ONƷSW2⿉OFF⾸Zone 3Group 33 to 48⾷SW1⿉OFFƷSW2⿉ON⾸Zone 4Group 49 to 64⾷SW1⿉ONƷSW2⿉ON⾸Switches⾷SW1ɿ2ɿ3⾸ON/OFF controller Main/SubMain (SW3 OFF) Sub (SW3 ON)OFF OFF OFF OFF OFF ONON OFF OFF ON OFF ONOFF ON OFF OFF ON ONON ON OFF ON ON ON[SW4] Central control Main/Sub setting(Main: OFF Sub: ON) When using only one ON/OFF controller, set this toMain (OFF). When using this unit in combination with other centralcontrol devices such as an intelligent controller or a systemcontroller, setting this unit to Sub (ON) is recommended.Note that when using “[SW5•6•7] Prohibition setting”,set this to Main (OFF). When using more than one ON/OFF controllers in acondition other than , set one unit to Main (OFF) andthe others to Sub (ON).[SW5•6•7] Remote control prohibition settingThe remote control operations (operation/stop) areprohibited for groups for which the prohibition setting ismade. This can be used when “[SW4] Switching Main/Sub setting of the central control” is set to Main (OFF).[SW8] ALL ON/ALL OFF target group settingSets the target to operate/stop when the “ALL ON” or “ALLOFF” button is pressed.1 Set this to OFF when all the groups in the zone selectedfor “[SW1•2] Zone address setting” are targeted.2 Set this to ON when only groups for which the prohibitionsetting is made are targeted.Group 1 to 16 : PermittedGroup 1 to 16⿉ProhibitedGroup 1 to 4⿉PermittedGroup 5 to 16⿉ProhibitedGroup 1 to 8⿉PermittedGroup 9 to 16⿉ProhibitedSwitches⾷SW5ɿ6ɿ7⾸Group 1 to 12⿉PermittedGroup 13 to 16⿉ProhibitedProhibition setting disabledON OFF OFFOFF OFF OFFOFF ON OFFON ON OFFOFF OFF ONON ON ONENGLISH