EN-4Outing function is a function that prevents the room temperature from increasing too much (ordecreasing too much) when no one is in the room.An air conditioner works automatically if this function is set effective.3. Outing FunctionCOOL / DRY① The air conditioner starts operation when the roomtemperature increases up to –1°C of the upperlimit.② The air conditioner stops operation when the roomtemperature decreases up to –2°C of the upperlimit.Room temperatureOuting function upper limitHEAT① The air conditioner starts operation when the roomtemperature decreases up to +1°C of the lowerlimit.② The air conditioner stops operation when the roomtemperature increases up to +2°C of the lowerlimit.Room temperatureOuting function Lower limitGeneral Performance of the Outing Function[Precautions]・The outing control only starts/stops the air conditioner. It does not change the operation mode/temperature setting.Therefore, the operation mode/temperature needs to be set beforehand so that the outing functionturns on the air conditioner with your desired operation mode/ temperature setting.・If the room temperature rapidly changes, the room temperature may get over the upper or lower limitwhen the outing function is activated.・The outing function is invalid during FAN/AUTO operation mode.・The air conditioner's stop order (stated in ② ⁄ above) is valid only when the outing function isoperated.If operated using other remote control units (or a centralized control device such as a system control),the outing function will not stop air conditioner operation.ENEN