6.3 Scale Conversion6-76.3 Scale Conversion Overview of functions• This function makes it possible to set an easy-to-use analog output range. Analog inputdata acquired in a range between preset minimum and maximum values is scale convertedand stored in the I/O area. This function is convenient if used for scale unit conversion.• Scale conversion is executed on a channel-by-channel basis.• Conversion values read from the analog input unit include fractions. Therefore, convert thevalues to easy-to-handle figures if needed.Scaleconversion(K)25000125001 3 5 (V)10000(K)50001 3 5 (V) ConfigurationName Default Setting range and descriptionFunctionsettingScaleconversionNotexecuteSelect “Execute.”Minimum valueof scale conversionK0 Set the minimum value at the time of using the scale conversionfunction.Setting range: -30,000 to +30,000 (specified with a signed integer)Maximum valueof scale conversionK10,000 Set the maximum value at the time of using the scale conversionfunction.Setting range: -30,000 to +30,000 (specified with a signed integer)* If data outside the minimum or maximum scale is input, scale conversion will be disabled and the minimum ormaximum scale value will be stored as a conversion value.Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com