9.1 High-level Instructions Used for EtherNet/IP Control9-199.1.5 EtherNet/IP Input Refresh (EIP_IN) Instruction formatR0EIP_IN U1S1U1 DT2000S2 DNote) A target unit for the instruction is specified with UNITSEL beforehand. Operation unit (i)There is no operation unit. List of operandsOperand DescriptionS1 Specify the target node number of the input refresh.S2 Specify the target connection number of the input refresh.D Specify the device address storing refresh results. Available devices (●: Available)Operand16-bit device 32-bit device IntegerRealnum-berString IndexmodifierWX WY WR WL WS SD DT LD UM WI WO TSCSTECE IX K U H SF DF " "S1 ● ● ● ● ● ● ● ● ●S2 ● ● ● ● ● ● ● ● ●D ● ● ● ● ● ● ● Processing• This instruction refreshes data only when new data is received for the target connection ofthe refresh.• (Input refresh: Data is copied to the device allocated from the receive buffer.) Precautions during programming• Call this instruction after X6B (EtherNet/IP preapration done) turns ON. If it is called beforeX6B turns ON, the EtherNet/IP communication preparation incomplete error is returned.• Do not execute this instruction continuously in one scan from the viewpoint of suppressingthe load.• Execute the refresh instruction after confirming that the communication of a specifiedconnection is performed normally using the cyclic communication normal node table.