145-2-4 MODE3(Mode for setting of each parameter for serial communication (RS-485))<MODE>+< V >Station number setting mode N O .Mode defines an individual station no. for each unit when two or more units communicate viaserial communication (RS-485).・It can be set the range of 01 to 99.Transmission speed (Baud rate) setting mode S P Mode defines serial communication (RS-485) transmission speed. Define the transmissionspeed according to the master’s (PLC etc.).・Select from 38400/19200/9600/4800/2400【bit/s】.Transmission format setting mode F TMode defines serial communication (RS-485) transmission format (Data length, Parity). Definethe transmission format according to the master’s (PLC etc).・Select from 8bit-o/7bit-n/7bit-E/7bit-o/8bit-n/8bit-E for MEWTOCOL type.8bit-o/8bit-n/8bit-E for MODBUS type.“n(none)” means parity is not available.“E(Even)” means parity is even number.“o(odd)” means parity is odd number.Response time setting mode R E S PMODE defines serial communication (RS485) response time of main unit.When command is received, it sends response after setting response time passes.・It can be set the range of 5 to 99ms.Normal display↓ MODE display↓ < V >Station number setting mode Factory setting / Display・Enter the station number using , < A >.・Station number can be entered the range of 01 to 99.↓ Transmission speed setting mode Factory setting / Display・Press to change transmission speed.・Transmission speed is selected from19200→9600→4800→2400→38400.↓ Transmission format setting mode Factory setting / Display・Press to change transmission format(Data length / Parity).・Transmission format is selected from8bit-o→7bit-n→7bit-E→7it-o→8bit-n→8bit-E.・n: not available E: even number o: odd number↓