94. ELECTRICAL WIRING4-1. General Precautions on Wiring(1) Before wiring, confirm the rated voltage of the unit as shown on its nameplate, then carry out the wiring closely following the wiringdiagram.WARNING(2) This equipment is strongly recommended to be installed with Earth Leakage Circuit Breaker (ELCB) or Residual CurrentDevice (RCD). Otherwise, it may cause electrical shock and fire in case of equipment breakdown or insulation breakdown.Earth Leakage Circuit Breaker (ELCB) must be incorporated in the fixed wiring in accordance with the wiring regulations.The Earth Leakage Circuit Breaker (ELCB) must be an approved 15 A, having a contact separation in all poles.(3) To prevent possible hazards from insulation failure, the unit must be grounded.(4) Each wiring connection must be done in accordance with the wiring system diagram. Wrong wiring may cause the unit to misoperate orbecome damaged.(5) Do not allow wiring to touch the refrigerant tubing, compressor, or any moving parts of the fan.(6) Unauthorized changes in the internal wiring can be very dangerous. The manufacturer will accept no responsibility for any damage ormisoperation that occurs as a result of such unauthorized changes.(7) Regulations on wire diameters differ from locality to locality. For field wiring rules, please refer to your LOCAL ELECTRICAL CODESbefore beginning.You must ensure that installation complies with all relevant rules and regulations.(8) To prevent malfunction of the air conditioner caused by electrical noise, care must be taken when wiring as follows:● The remote control wiring and the inter-unit control wiring should be wired apart from the inter-unit power wiring.● Use shielded wires for inter-unit control wiring between units and ground the shield on single side.(9) If the power supply cord of this appliance is damaged, it must be replaced by a repair shop designated by the manufacturer, becausespecial-purpose tools are required.4-2. Recommended Wire Length and Wire Diameter for Power Supply SystemIndoor unitType Time delay fuse orcircuit capacityY2 15 AControl wiring(A) Inter-unitcontrol wiring(between outdoorand indoor units)(B) Remote controlwiring(C) Control wiringfor group controlAWG #18(0.75 mm 2)Use shielded wiring*AWG #18(0.75 mm2)Use shielded wiring*AWG #18(0.75 mm2)Use shielded wiring*Max. 3,280 ft.(Max. 1,000 m)Max. 1,640 ft.(Max. 500 m)Max. 650 ft. (Total)(Max. 200 m (Total))NOTE* With ring-type wire terminal.