5-345(1) Press and hold the and buttonssimultaneously for 4 seconds or longer.(2) The unit No. “X-X” (main unit No.), item code “ ”(sensor address), and servicing monitor “ ”(sensor temperature) are displayed on the remotecontroller LCD display.(3) Press the temperature setting /and select the item code to the address of thebuttonssensor to monitor.(4) If group control is in effect, press theto select the unit to monitor.buttonPress the temperature setting buttons to select theitem code to change.(5) Press the button to return to normal remotecontroller display.(4)(3)(4)(3)(4) (5) (1)(2)5-6. Sensor Temperature Display Function(Displayed regardless of operation and stop)The procedure below displays the sensor temperatures from the remote controller, indoor unit, and outdoor unit onthe remote controller.NOTEThe temperature display appears as “- - - -” for units that are not connected.* If monitor mode is engaged while normal operation is in progress, only the parts of the LCD display shown in thefigure will change. Other parts continue to display the same information as during normal operation.Item code Meaning of CodeIndoor unit data 02 Indoor unit intake temp.03 Indoor unit heat exchanger temp. (E1)04 Indoor unit heat exchanger temp. (E2)05 –06 –07 –08 ––09Outdoor unit data 0A Discharge temp. (TD)0b ––0COutdoor unit heat exchanger temp. (C2)0d Intake temp. (TS)0E Outdoor unit heat exchanger temp. (C1)0F10 –11 Outdoor air temp. (TO)12 ––1314 Current value (CTL1)Current value (CTL2)15 Outdoor MV value (MOV1)1619 Frequency* Depending on the model, some items may not be displayed.Sensor Temperature Correlation TableAMP Air Conditioningwww.ampair.co.uk | sales@ampair.co.uk