73-2. Suspending the Indoor UnitDepending on the ceiling type:1. Check the suspension bolt pitch.2. Ensure that the ceiling is strong enough to support the weight of the unit.3. To prevent the unit from dropping, firmly fasten the suspension bolts as shown in the figure below.L*20 ~ 50Hole-in-anchorHole-in-plug InsertUnit: mmConcreteSuspension bolt(field supply)Hexagonal nut (field supply)Special washer (field supply)Special washer (field supply)Hexagonal nut (field supply)Suspension bolt (field supply)Hexagonal nut (field supply)Special washer (supplied)Suspension lug* Choose “L” dimension according to the status of the ceiling.Fig. 3-3 Fig. 3-4NOTEType 200Suspension bolt(field supply) M10 or 3/8”WARNINGIt is important that you use extreme care in supporting the indoor unit inside the ceiling.ensure that the ceiling is strong enough to support the weight of the unit.Before suspending the unit, test the strength of each attached suspension bolt.(1) When placing the unit inside the ceiling, determine the pitch of the suspension bolts referring to the dimensional data given previously.Tubing must be laid and connected inside the ceiling when suspending the unit.If the ceiling is already constructed, lay the tubing into position for connection to the unit before placing the unit inside the ceiling.(2) Screw in the suspension bolts allowing them to protrude from the ceiling as shown in Fig. 3-3. (Cut the ceiling material, ifnecessary.)(3) Suspend and fix the indoor unit using the 2 hexagonal nuts (field supply) and special washers (supplied with the unit) as shown inFig. 3-4.CAUTION• The top of the unit must be installed horizontally.• Check the unit is placed horizontally.Make sure the unit is installed level using a level or a vinyl hose filledwith water.In using a vinyl hose instead of a level, adjust the top surface of the unit tothe surface of the water at both ends of the vinyl hose and make horizontaladjustment on all 4 corners of the unit.If the air discharge side of the unit is installed downward, splashing wateror water leak may occur.Also, the dust may accumulate inside the drain pan caused by drainingresidual water.• When lifting the unit, do not attempt to hold the electrical component boxin hand.• Do not leave the drain pan of the unit downward for long hours.If doing so, the insulation material can be crushed.Crushed insulation can lead to condensation.HorizontallevelVinyl hose filled with waterCarpenter’s levelElectrical component boxDrain panVinyl hose filledwith waterInsulationmaterial