6-766-5. Monitoring the Outdoor Unit Alarm History: Display of Outdoor Unit Alarm HistoryDisplays outdoor unit alarms only. Does not display indoor unit alarms.Check the indoor unit alarm histories separately using the indoor unit remote controllers or other control device.(1) Press and hold the button and button simultaneously for 4 seconds orlonger to change to outdoor unit alarm history mode.During the alarm history display, “Service Check” is lit.The display and operations are the same as the monitoring of the alarm devicehistory that is performed using the unit remote controller. However, the outdoorunit address appears instead of the unit No.↓(2) Press the button and select the outdoor unit for alarm history monitoring.↓(3) Use the temperature setting and buttons to select the item codefor the alarm history.The display shows the address of the selected outdoor unit, the item code, and the alarm history (alarm data).The outdoor unit address is displayed as system XX-YY.System XX = Outdoor unit system address↓YY = Outdoor unit sub-bus addressThe item code is displayed as 01 – 08. 01 indicates the most recent alarm.The alarm history is indicated by the alarm code. (If there have been no alarm codes, “ ” is displayed.)(4) To clear the alarm history, press the button. (The outdoor unit alarm history will be cleared.)↓(5) To end, press the button. The display returns to the normal remote controller display.6-6. Settings Modes: Setting the Outdoor Unit EEPROMSetting mode 1(1) Press and hold the button and button simultaneously for 4 seconds or longer.(2) Use the temperature setting and buttons to changethe item code. The item codes and setting data are shown in thetable of “List of Item Codes” on the next page.(3) Use the timer time and buttons to change the setting data.To confirm the changed setting data, press the button.(At this time, “Setting” stops blinking and remains lit.)(4) During this mode, “Setting” is displayed, blinking. The outdoor unitaddress display section displays “ALL,” the item code and number(DN value in the table), and the setting data (6 digits).(The setting data is displayed in 6 digits. The display changesbetween the first 3 digits (Fig. A ) and the last 3 digits (Fig. B ).When the first 3 digits are displayed, the top point of the colon islit.)(5) To end the setting mode, press the button.**(5) (1) (4) (2)(3)AB(3)(1)(2)(5)(3)(1)(2)(5)Display of first 3 digitsDisplay of last 3 digitsA and B are displayed alternately.(Example shows display of 000 001.)