2 - 39Remote Control Functions3. Timer Remote Controller1234567Selecting the DC fan motor tap (when setting from the PCB)● 4-way Air Discharge Semi-Concealed type Stop the system before performing these steps.Open the electrical component box cover, then check the indoor unit control PCB.Connect the jumper connector (2P: yellow) which was supplied with the accessory to the correct connector pinon the indoor unit control PCB according to the setting number which was confirmed in Table 1 (Table of DCFan Motor Tap Settings).• If the setting No. is (1), then connect the jumper connector to the connector pin TP1 (2P: red) on the indoor unitcontrol PCB.• If the setting No. is (3), then connect the jumper connector to the connector pin TP3 (2P: yellow) on the indoor unitcontrol PCB.● Suspended type Stop the system before performing these steps.Open the electrical component box cover, then check the indoor unit control PCB.Connect the jumper connector (2P: yellow) which was supplied with the accessory to the correct connector pinon the indoor unit control PCB according to the setting number which was confirmed in Table 2 (Table of DCFan Motor Tap Settings).• If the setting No. is (1), then connect the jumper connector to the connector pin TP1 (2P: red) on the indoor unitcontrol PCB.• If the setting No. is (3), then connect the jumper connector to the connector pin TP3 (2P: yellow) on the indoor unitcontrol PCB.● 1-way Air Discharge Semi-Concealed type Stop the system before performing these steps.Open the electrical component box cover, then check the indoor unit control PCB.Connect the jumper connector (2P: yellow) which was supplied with the accessory to the correct connector pinon the indoor unit control PCB according to the setting number which was confirmed in Table 3 (Table of DCFan Motor Tap Settings).• If the setting No. is (1), then connect the jumper connector to the connector pin TP1 (2P: red) on the indoor unitcontrol PCB.• If the setting No. is (3), then connect the jumper connector to the connector pin TP3 (2P: yellow) on the indoor unitcontrol PCB.TP6White Yellow RedTP3 TP1 PreviousNext |