447-4. Auto Address SettingBasic wiring diagram: Example (1)• If link wiring is not used(The inter-unit control wires are not connected to multiple refrigerant systems.)Indoor unit addresses can be set without operating the compressors.1 2 3 3211 321 221 3321(S006) (S007)(S005)(S004)(S003)(S002)11-1 1-2 1-3 1-10(S007) (S007)0Case 1(1) Automatic Address Setting from the Outdoor Unit1. To set the number of outdoor units, on the outdoor main unit control PCB set the No. of outdoor units DIP switch (S006) to1 2 3(3 units), and set the unit No. DIP switch (S007) to2 31(unit No. 1 – main outdoor unit).2. On the No. 2 (sub) unit control PCB, set the unit No. switch (S007) to321(unit No. 2).On the No. 3 (sub) unit control PCB, set the unit No. switch (S007) to1 2 3(unit No. 3).3. On the outdoor main unit control PCB, check that the system address rotary switch (S002) is set to “1” and that the DIPswitch (S003) is set to1 2“0.” (These are the settings at the time of factory shipment.)4. To set the number of indoor units that are connected to the outdoor unit to 10 on the outdoor main unit control PCB, set theNo. of indoor units DIP switch (S005) to2 31“1,” and set the rotary switch (S004) to “0.”5. Turn ON the power to the indoor and outdoor units.6. On the outdoor main unit control PCB, short-circuit the automatic address pin (CN054) for 1 second or longer, then release it.↓(Communication for automatic address setting begins.)↓* To cancel, again short-circuit the automatic address pin (CN054) for 1 second or longer, then release it.The LED that indicates that automatic address setting is in progress turns OFF and the process is stopped. Be sureto perform automatic address setting again.(Automatic address setting is completed when LEDs 1 and 2 on the outdoor main unit control PCB turn OFF.)↓7. Operation from the remote controllers is now possible.* To perform automatic address setting from the remote controller, perform steps 1 to 5, then use the remote controller andcomplete automatic address setting.● Refer to “Automatic Address Setting from the Remote Controller.”No. 1 (main outdoor unit)No. 2 (sub unit) No. 3 (sub unit)UnitNo. 3(Sub)UnitNo. 2(Sub)UnitNo. 1(Main)Outdoor UnitIndoor UnitRemote controllerRemote controllercommunication wiringLeave the socket that isused to short-circuit theterminal plug.(CN072)Inter-outdoor unitcontrol wiringInter-unit control wiringInter-outdoor unitcontrol wiringsettingssettings settingsNo. of indoor units(10 units setting)System address(system 1 setting)No. ofoutdoorunits (3unitssetting)Unit numbersetting(Unit No. 1)Unitnumbersetting(Unit No. 2)Unitnumbersetting(Unit No. 3)ONON ONONON ONONON ONONON ONOFFOFF OFFOFFOFF OFFFig. 7-5ONONONONONONONONONOFFOFFOFF