Terminal Descriptions 6-1512C Series ConverterChapter 6 TERMINAL DESCRIPTIONSControl TerminalsTERMINAL FUNCTION DESCRIPTION NOTEST1 Tacho Feedback Motor Mounted Tachogenerator Input.Proportional to Motor Speed+350 Vdc Max. Approx.110 kohm.T2 Not ConnectedT3 Speed Meter Output Analogue Output, 0 to +10V for 0 to 100%speed.5mA outputS/C protectedT4 Minimum Speed Setpoint Potentiometer return, minimum speedadjustable 0 to 30% with 10K setpointpotentiometer.Must be used inconjunction with asetpoint potentiometerT5 Run Digital Input to Run Controller.+10V to +24V to Run.0V to Stop.T6 Current Meter Output Analogue Output, 0 to +10VScalingSW8 = On 5V= 100% Calibrated CurrentSW8 = Off 5V= 100% Controller Current5mA outputS/C protectedT7 Torque/Current Limit Analogue Input,0 to +7.5V = 0 to 150% of Calibrated CurrentT8 0V Common Analogue / Digital Signal CommonT9 Setpoint Ramp O/P Analogue Output,0 to +10V = 0 to 100% Ramped Setpoint5mA outputS/C protectedT10 Aux. Speed Setpoint Analogue Input,0 to +10V = 0 to 100% Speedapprox100 kohmT11 0V Common Analogue / Digital Signal CommonT12 Total Setpoint O/P Analogue Output,0 to +10V = 0 to 100% Speed5mA outputS/C protectedT13 Setpoint Ramp I/P Analogue Input,0 to +10V = 0 to 100% Speedapprox100 kohmT14 +10V Reference Analogue Output,+10V Reference for Speed/ Current Setpoints5mA outputS/C protectedT15 Stall Override Digital Input to Override Stall Detection+10V = Overrideapprox100 kohmT16 -10V Reference Analogue Output,-10V Reference for Speed/ Current Setpoints5mA outputS/C protectedT17 Not ConnectedT18 Not ConnectedT19 Health Output Digital Output,+24V = Healthy50mA SourceUnprotectedT20 Not ConnectedT21 Not ConnectedT22 Not ConnectedT23 Zero Speed Output /Zero Setpoint OutputDigital Output,+24V = Running0V = Stopped50mA SourceUnprotectedT24 Not ConnectedThis manual was downloaded on www.sdsdrives.com+44 (0)117 938 1800 - info@sdsdrives.com