11-1 Technical Specifications512C Series ConverterChapter 11 TECHNICAL SPECIFICATIONSEnvironmental RequirementsEnclosure Chassis Mounting IP00.Operating Temperature 0 to +40oC. (Derate 1.5%/Degree above 40oC)Humidity 85% R.H. at 40oC. (non condensing)Altitude Above 1000m derate at 1% / 100m to amaximum of 2000mStorage Temperature -25oC to +55oCTransport Temperature -25oC to +70oCClimatic Conditions Class 3k3, as defined by EN50178 (1998)Operating ConditionsInstallation Category Overvoltage Category IIIPollution Pollution Degree 2.Maximum Supply Voltages(Derived from a 3-phase480Vac L - L Non earth referenced (IT)or earth referenced (TN)supply) 480Vac L - N Earth referenced (TN)Wiring Control Cabling 0.75sq.mm minimum. Power cable to be minimum 600V AC rated at 1.5 x armature current. High speed semi-conductor fuses of the correct rating are recommended controller semi-conductor protection, as the 512C is not internally fused. The suitability of the semi-conductor fuse branch protection should be decided by the installer. Ensure a protective earth connection is made compatible with the rating. Isolated control wiring should not be run close to the power cabling. If screened cables areused (recommended on setpoints and tachogenerators) connect screens to earth only atcontroller end. Parker Hannifin Manufacturing Limited can supply fuse assemblies which can be bulkheadmounted and also act as convenient supply isolators.This manual was downloaded on www.sdsdrives.com+44 (0)117 938 1800 - info@sdsdrives.com