DOC-0017-03-EN: AC15 Series - Hardware Installation ManualDOC-0017-03-EN-B 04.04.2023 39 (125)7.2 External EMC FiltersAdditional external EMC filters are sometimes required to meet specific conducted emissions standardsand environments.All products have internal filters that meet the Category C3 limits defined in EN61800-3. Where thisperformance is not adequate for a customer’s application, the Conducted Emissions plots provided in‘Chapter 11: Compliance’ allow for the selection or design of an additional external EMC filter to meetcustomer’s needs.EMC advice to consider during the product installation can also be found in this section.7.3 AC Line ChokesAn External AC Line Choke may be required on the line supply to the drive:1. On supplies delivering >12kA but <50kA RMS symmetrical Amperes, 480V maximum.2. To mitigate supply quality issues.Where required, Parker suggest the following AC Line Choke ratings:1ø, 230V ProductsFrameSize Product CodeMotorPower(kW)Inductance(mH/phase)Rated Current(A)Peak Current@150% HDRating (A)115G-11-0025... 0.37 2.525 5.8 1215G-11-0045... 0.75 1.464 10 2115G-11-0070... 1.5 1.046 14 302 15G-12-0100... 2.2 0.732 20 42Notes:- AC Line Choke inductance values calculated @230V, 50Hz- AC Line Choke impedance is nominally 3% of drive rating- AC Line Choke maximum voltage rating should be 240V +10%, TN/IT- AC Line Choke frequency of operation is 50 – 60Hz- AC Line Choke inductance during 150% overload operation should be >90% of its nominal value3ø, 230V ProductsFrameSize Product CodeMotorPower(kW)Inductance(mH/phase)Rated Current(A)Peak Current@150% HDRating (A)115G-31-0025... 0.37 3.019 3.5 7.415G-31-0045... 0.75 1.957 5.4 1115G-31-0070... 1.5 1.355 7.8 172 15G-32-0100... 2.2 0.961 11 233 15G-33-0170... 4 0.571 18.5 394 15G-34-0210... 5.5 0.480 22 475 15G-35-0300... 7.5 0.341 31 6615G-35-0400... 11 0.258 41 87