Page 16Drive Start-upBefore Applying Power :• Read the Safety section at the front of the QuickStart.• Ensure that all local electric codes are met.• Check for damage to equipment.• Check for loose ends, clippings, filings, drilling swarf etc. lodged in the drive andsystem.• Check all external wiring circuits of the system - power, control, motor and earthconnections.• Ensure that unexpected rotation of the motor in either direction will not result indamage, bodily harm or injury. Disconnect the load from the motor shaft, if possible.• Check the state of the Motor Thermistor and Brake Resistor connectors. Checkexternal run contacts are open. Check external speed setpoints are all at zero.• Ensure that nobody is working on another part of the system which will be affectedby powering up.• Ensure that other equipment will not be adversely affected by powering up.• Check motor stator connections are correctly wired for Star or Delta as necessary fordrive output voltage.Drive Set-upAppendix A contains information about the Keypad menus and parameter names.Motor DataBefore attempting to set up the drive, you will need some motor information. This is found on the motornameplate. The information you will need is listed below:Base VoltsBase frequencyBase RPMFull load ampsNo load amps (mag current)Connection (star or delta)If all connections have been checked, it is time to POWER-UP the drive