Parker EME Conditions of utilization for UL approval PSUP192-120147N9 PSUP Manual 2019-06 111.7 Conditions of utilization for UL approval PSUPUL approval for mains modules PSUPConform to UL: in accordance with UL508CCertified E-File_No.: E142140The UL approval is documented by a“UL” logo on the device (typespecification plate).UL approval PSUP30 in preparation!Conditions of utilization The devices are only to be installed in a degree of contamination 2 environment(maximum). The devices must be appropriately protected (e.g. by a switching cabinet). Tightening torque of the field wiring terminals ( green Phoenix plugs)Device X40: Ballast resistor X41: Mains connector X9: 24VDCPSUP10 0.5 Nm (4.43Lb.in) 1.2 Nm (10.62Lb.in) 1.2 Nm(10.62Lb.in)PSUP20 0.5 Nm (4.43Lb.in) 1.7 Nm (15Lb.in) 1.2 Nm(10.62Lb.in)PSUP30 UL approval in preparation Temperature rating of field installed conductors shall be at least 60°C. Usecopper lines onlyPlease use the cables described in the accessories chapter, they feature atemperature rating of at least 60°C. Maximum Surrounding Air Temperature: 40°C. Control voltage supply (24VDC) only permissible with "class 2" power supply. Suitable for use on a circuit capable of delivering not more than 5000 rmssymmetrical amperes and 480 volts maximum and protected by (see below). The devices need a "branch circuit protection".PSUP10D6Maximum fuse rating perdeviceMeasure for line and device protection:MCB miniature circuit breaker (K characteristic) 25A inaccordance with UL category DIVQ(ABB) S203UP-K25 (480VAC)PSUP20D6Maximum fuse rating perdevice2 special purpose fuses in lineare requiredCable protection measure:MCB (K characteristic) with a rating of 50A / 4xxVAC(depending on the input voltage).(ABB) S203U-K50 (440VAC)Device protection measure:Fuses 80A / 700VAC per supply leg in accordance with ULcategory JFHR2:Bussmann 170M1366 or 170M1566DCaution!Risk of electric shock.Discharge time of the bus capacitor is 10 minutes.