ENGLISH RAIS - manual for Q-BIC & Q-BIC insert20Using not insulated smoke pipe, the minimum distance to combustible wall must be 225mm from smoke pipe.Installation distance in case of non-combustible wallWe recommend a minimum distance to non-combustible material of 50 mm (F) for cleaningconsiderations.It should always be possible to access the accessdoor.Installation distance in case of combustible wallTo find out whether the wall next to where the stove is going to be installed is flammable,you should contact your building contractor or the local building authorities.The hearth should be able to accommodate the weight of the stove. The chimney must beindependently supported by wall brackets or a ceiling support plate. The weight of the stoveis indicated in the brochure.The stove should always be installed on a non-combustible hearth of a size and constructionthat is in accordance with the provisions of the current UK Building Regulations ApprovedDocument J.If the stove is to be installed on a wooden floor, it must be covered with a noncombustiblematerial at least 12mm thick, in accordance with UK Building Regulations Approved Docu-ment J, to a distance of 300 mm in front of the stove and 150 mm to each side measuringfrom the door of the combustion chamber.The clearance distances to combustible material beneath, surrounding or upon the hearthand walls adjacent to the hearth should comply with the guidance on the separation of com-bustible material given in UK Building Regulations Approved Document J and also in thesestove instructions.