Regency HZ33CE-10 Gas Fireplace | 31|31installationGAS PIPE PRESSURETESTINGThe appliance must be isolated from the gassupply piping system by closing its individualmanual shut-off valve during any pressuretesting of the gas supply piping system at testpressures equal to or less than 1/2 psig. (3.45kPa). Disconnect piping from valve at pressuresover 1/2 psig.The manifold pressure is controlled by a regulatorbuilt into the gas control, and should be checkedat the pressure test point.Note: To properly check gas pressure, bothinlet and manifold pressures shouldbe checked using the valve pressureports on the valve.1. Make sure the valve is in the "OFF" position.2. Loosen the "IN" and/or "OUT" pressure tap(s),turning counterclockwise with a 1/8" wide flatscrewdriver.3. Attach manometer to "IN" and/or "OUT"pressure tap(s) using a 5/16" ID hose.4. Light the pilot and turn the valve to "ON"position.5. The pressure check should be carried outwith the unit burning and the setting shouldbe within the limits specified on the safetylabel.6. When finished reading manometer, turnoff the gas valve, disconnect the hose andtighten the screw (clockwise) with a 1/8" flatscrewdriver. Note: Screw should be snug,but do not over tighten.HIGH ELEVATIONThis unit is approved in Canada for altitude to4500 ft. (CAN/CGA-2.17-M91.. For Natural Gasinstallations above 4500 ft. follow current CAN/CGA-B149.1.HZ33CE-NG10 System DataConversion Kit# 433-971 (NG to LP)For 0 to 4500 feet altitudeBurner Inlet Orifice Sizes: #47Max. Input Rating 17,000 Btu/hMin. Input Rating 12,000 Btu/hSupply Pressure min.5.0" w.c.Manifold Pressure(High) 3.5"+/- 0.3" w.c.HZ33CE-LP10 System DataFor 0 to 4500 feet altitudeBurner Inlet Orifice Sizes: #56Max. Input Rating 1 5 , 0 0 0 B t u / hMin. Input Rating 1 2 , 5 0 0 B t u / hSupply Pressure min.11.0" w.c.Manifold Pressure(High) 10"+/- 0.4"w.c.PILOT ADJUSTMENTNote: If you have an incorrect flame pattern,contact your Regency® dealer forfurther instructions.Incorrect flame pattern will have small,probably yellow flames, not coming intoproper contact with the rear burner or flamesensor.Periodically check the pilot flames. Correctflame pattern has two strong blue flames:1 flowing around the flame sensor and 1flowing across the burner (it does not haveto be touching the burner).BurnerFlame SensorPilot Ignitor885 S.I.T. VALVEDESCRIPTION1) 6 Stage flame adjustment2) Pilot adjustment3) Inlet Pressure Tap4) Outlet Pressure Tap5) Pilot Outlet6) Main Gas Outlet7) Main Gas Inlet123471234657